OSHPD Certified POWER WAVE

Single Phase Unit
Specification
PDF Format
Data Sheets
Technical Drawings
Bypass Panel Assembly Drawings
User manual
Shaker Table testing
OSHPD Certificate
GMS Brochure

 

Three Phase Unit
Specification
PDF Format
Data Sheets
Technical Drawings
Bypass Panel Assembly Drawings
User manual
Shaker Table testing
OSHPD Certificate
GMS Brochure

 


Single Phase Features Three Phase Features
CSA Listed to UL1778 and UL924
Incandescent, Fluorescent, HID, HPS
Power Factor & Energy Efficient Ballast
90% Efficiency
Sinusoidal Waveform
Pulse Width Modulated (PWM)
Generator Compatible
Multiple Output Voltages
LCD Panel for Monitoring
Modular Assy for Ease of Installation
Transformerless Technology
Battery Exerciser
Continuous Self-Diagnostics
Double Conversion Technology
Input Power Correction Built-In
Stackable Cabinets
Seismic Rated with Bracket Kit
Remote Monitoring
RS-232 & 485
Optional Global Monitoring System (GMS)
2 Year Factory Warranty

CSA Listed to UL1778 and UL924
Incandescent, Fluorescent, HID, HPS
Power Factor & Energy Efficient Ballast
90% Efficiency
Sinusoidal Waveform
Pulse Width Modulated (PWM)
Generator Compatible
LCD Panel for Continuous Self Diagnostics
Modular Assembly for Ease of Installation
Battery Exerciser
Double Conversion Technology
Stackable Cabinets
Seismic Rated with Bracket Kit
Remote Monitoring
RS-232 & 485
Optional Global Monitoring System (GMS)
2 Year Factory Warranty


Specifications

  Specifications
Single Phase Power Wave
Three Phase Power Wave
  Power Rating 3.0, 5.0, 6, 7.5, 8, 10, 12.5, and 15 KW 8, 12, 16, 20, 24, 32, 40, and 50 KW
  Input Voltage

3, 6, 8KW;120, 208, 240, 277, or 480 VAC (-20% to +15%)

7.5, 10, 17 KW; 208, 240, 277, or 480 VAC (-15% to +15%)

208Y/120 or 480Y/277 VAC (-20% to +15%)
  Output Voltages 208, 240, 277, or 480 VAC 208Y/120 or 480Y/277 VAC
  Output Frequency
  (Inverter Operation)
60 Hz ±0.5 Hz 60 Hz ±0.5 Hz
  Voltage Regulation ±3%, Regulated within CBEMA curve ±3%, Regulated within CBEMA curve
  Output Wave Form Sine-Wave < 5% THD. Sine-Wave < 5% THD.
  Efficiency

94% On-Line (typ.)
98% Fast Transfer (typ.)

94% On-Line (typ.)
98% Fast Transfer (typ.)
  Crest Factor 3:1 Typical 3:1 Typical
  Surge Protection The UPS will protect itself and the load against surges as defined in ANSI/IEEE C62.41 Categories A and B. The UPS will protect itself and the load against surges as defined in ANSI/IEEE C62.41 Categories A and B.
  Isolation Complete from line. Output neutral bonded to ground Complete from line. Output neutralbonded to ground
  Noise Isolation -120 dB Common-Mode; -60 dB Transverse-Mode -120 dB Common-Mode; -60 dB Transverse-Mode
  Battery Sealed maintenance-free (AGM) battery Sealed maintenance-free (AGM) battery
  Recharge Current Conforms to UL Standards Conforms to UL Standards
  External Battery Provisions for hardwire connection of optional external battery cabinets or DC source. Provisions for hardwire connection of optional external battery cabinets or DC source.
Environmental
  Humidity 0 - 95% RH w/ no condensation 0 - 95% RH w/ no condensation
  Operating Temperature 0° to 40°C. (32° - 104°F) UPS: 0° to 40°C. (32° - 104°F)
Battery: 20° to 30°C. (68° - 86°F)
  Storage Temperature -20° to 60°C. (-4° - 140°F) -20° to 60°C. (-4° - 140°F)
  Altitude Up to 10,000 ft Up to 10,000 ft
  Safety Agencies CSA Listed UL1778, UL924, MEA CSA Listed UL1778, UL924, MEA
  *Inverter Cabinet Sizes 3, 5, 6, 8kW: 39" Wide x 18" Deep x 68" High 39" Wide x 18" Deep x 68" High
   Cabinet Foot Prints 46" Wide x 18" Deep x 68" High 46" Wide x 18" Deep x 68" High
  *Inverter Cabinet Sizes 7.5, 10, 12.5, 15kW: 51" Wide x 30.5" Deep x 70" High  
  Cabinet Foot Prints 58.75" Wide x 30.5" Deep x 70" High  
  *Battery Cabinet Sizes   Refer to Datasheet
*Standard Battery Back-up time is 90 minutes @ full load