Host Power

Product Details
Specification
PDF Format
Data Sheets
Technical Drawings
User manual

Features

ETL Listed to UL1778
Incandescent, Fluorescent, HID, HPS
Power Factor & Energy Efficient Ballast
Sinusoidal Waveform
Pulse Width Modulated (PWM)
Generator Compatible
LCD Panel for Continuous Self Diagnostics
Modular Assembly for Ease of Installation
Intelligent Battery Test
Double Conversion Technology
Seismic Rated with Bracket Kit
Remote Monitoring
RS-232 & 485
Optional Global Monitoring System (GMS)
2 Year Factory Warranty

Emergency Lighting Inverter Central Lighting Inverter
Specifications

  Power Rating 10, 20, 30, 40, 50, 60, 80, 100, 120, 160 kVA (also available upon request 200, 240, 300, 400, 500 kVA)
  Input Voltage 208Y/120 or 480Y/277 VAC (-15% to +15%)
  Output Voltages 208Y/120 or 480Y/277 VAC
  Output Frequency
  (Inverter Operation)
60 Hz ±0.1 Hz
  Voltage Regulation ±1% at 100% unbalanced load
  Output Wave Form Sine-Wave < 2% THD.
  Crest Factor 3:1 Typical
  Surge Protection The UPS will protect itself and the load against surges as defined in ANSI/IEEE C62.41 Categories A and B.
  Isolation True galvanic isolated
  Battery Sealed maintenance-free VRLA or long life battery
  Recharge Current Varies per KVA and conforms to UL924
Environmental
  Humidity 0 - 90% RH w/ no condensation
  Operating Temperature UPS: 0° to 40°C. (32° - 104°F)
Battery: 20° to 30°C. (68° - 86°F)
  Storage Temperature -20° to 60°C. (-4° - 140°F)
  Altitude Up to 10,000 ft
  Cabinet Sizes
(UPS only)
10-60kVA: 34" Wide x 31.5" Deep x 63" High
80-160kVA: 55.5" Wide x 31.5" Deep x 63" High
200-320kVA: 86.5" Wide x 31.5" Deep x 63" High
400kVA: 133" Wide x 39.5" Deep x 71" High
500kVA: 178" Wide x 39.5" Deep x 71" High
  *Battery Cabinet Sizes Consult Factory
*Standard Battery Back-up time is 90 minutes @ full load