POWER WAVE 4

Product Details
Specification
PDF Format
Data Sheets
Technical Drawings
Seismic Certification
User manual

Features

ETL Listed to UL1778 and UL924
Incandescent, Fluorescent, HID, HPS
Power Factor & Energy Efficient Ballast
Sinusoidal Waveform
Pulse Width Modulated (PWM)
Generator Compatible
LCD Panel for Continuous Self Diagnostics
Modular Assembly for Ease of Installation
Intelligent Battery Test
Double Conversion Technology
Seismic Rated with Bracket Kit
Remote Monitoring
RS-232 & 485
Optional Global Monitoring System (GMS)
2 Year Factory Warranty

Emergency Lighting Inverter Central Lighting Inverter
Specifications

  Power Rating 60, 80, 100, 120, and 160 kVA, 0.8PF
200, 240, 300, 400, and 500 kVA are also available upon request
  Input Voltage 208Y/120 or 480Y/277 VAC (-15% to +15%)
  Output Voltages 208Y/120 or 480Y/277 VAC
  Output Frequency
  (Inverter Operation)
60 Hz ±0.1 Hz
  Voltage Regulation ±1% at 100% unbalanced load
  Output Wave Form Sine-Wave < 2% THD.
  Crest Factor 3:1 Typical
  Surge Protection The UPS will protect itself and the load against surges as defined in ANSI/IEEE C62.41 Categories A and B.
  Isolation True galvanic isolated
  Noise Isolation -120 dB Common-Mode; -60 dB Transverse-Mode
  Battery Sealed maintenance-free VRLA or long life battery
  Recharge Current Varies per KVA and conforms to UL924
Environmental
  Humidity 0 - 90% RH w/ no condensation
  Operating Temperature UPS: 0° to 40°C. (32° - 104°F)
Battery: 20° to 30°C. (68° - 86°F)
  Storage Temperature -20° to 60°C. (-4° - 140°F)
  Altitude Up to 10,000 ft
  Cabinet Sizes
(UPS only)
60-160kVA: 44" Wide x 31.5" Deep x 63" High
200-320kVA: 86.5" Wide x 31.5" Deep x 63" High
400kVA: 133" Wide x 39.5" Deep x 71" High
500kVA: 178" Wide x 39.5" Deep x 71" High
  *Battery Cabinet Sizes Consult Factory
*Standard Battery Back-up time is 90 minutes @ full load



       Copyright © 2002 Onlinepower, Inc. All rights reserved.